Plan Review Notes
Plan Review Notes For Permit 01120203
Permit Number 01120203
Review Stop E
Sequence Number 2
Notes
Date Text
2002-01-15 00:00:00******************* UNSAT *************
  
 PLEASE NOTE THAT NOT ALL NOTES FORM THE
 FIRST REVIEW WERE ADDRESSED.
  
 1)NOTE: PLEASE NOTE A ONE-LINE RISER
 DIAGRAM NEEDS TO BE SUBMITTED FOR REVIEW
 215-5
 2)NOTE: PLANS SHOW 3-#2`S BUT WHAT SIZE
 IS THE PANEL?215-5/310-15/AND ART 240
 FOR CORRELATION OF OCP.
  
 3)NOTE: PLEASE NOTE THAT THE PANEL
 SCHEDULE NEEDS TO SHOW OCP AND ALL WIRE
 SIZES, THE NOTE SAYS #12 AND 20A OCP,
 WHAT ABOUT RANGE? DRYER?
  
 4)NOTE: PLEASE NOTE PLANS SHOW A WATER
 HEATER, PLEASE CLARIFY IF GAS OR ELEC?
 IF ELEC, PLEASE LIST.
  
 5)NOTE: PLEASE NOTE, PLANS STILL MISSING
 FRONT AND REAR RECEPT, 210-52E
  
 6)NOTE: PLEASE NOTE THAT GROUNDING
 ELECTRODE SYSTEM NEEDS TO BE SHOWN ON
 RISER DIAGRAM ALSO. SHOW GROUNDING
 ELECTRODE SIZE PER 250-66 AND SHOW
 ELECTRODE SYSTEM PER 250-50 TO INCLUDE
 COLD WATER PIPE AND GAS BOND IF ANY.
  
 7)NOTE: PLEASE NOTE, OUTLET SPACING IS
 MISSING SOME OUTLETS REQ`D PER 210-52.
 BEDROOMS 1&2 AND KITCHEN.
  
 8)NOTE: PLEASE CLARFIY OUTLET SPACING
 FOR KITCHEN COUNTER. PLANS SHOW OUTLET
 ON WALL AT KITCHEN PENINSULAR, PLEASE
 CLARFIY. 210-52-C-1
  
 9)NOTE: PLEASE NOTE THAT SMOKE DETECTORS
 CAN NOT BE INSTALLED IN KITCHENS, OR
 BATHS PER NFPA-72 2-5.2.1.6
  
 10)NOTE: PLEASE CLARIFY "TWO" SMALL APPL
 CIRCUITS. 210-52B
  
 11)NOTE: PLEASE SUBMIT TWO COPIES OF
 PLANS FOR REVIEW.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372