| 2002-01-15 00:00:00 | ******************* UNSAT ************* |
| | |
| | PLEASE NOTE THAT NOT ALL NOTES FORM THE |
| | FIRST REVIEW WERE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE NOTE A ONE-LINE RISER |
| | DIAGRAM NEEDS TO BE SUBMITTED FOR REVIEW |
| | 215-5 |
| | 2)NOTE: PLANS SHOW 3-#2`S BUT WHAT SIZE |
| | IS THE PANEL?215-5/310-15/AND ART 240 |
| | FOR CORRELATION OF OCP. |
| | |
| | 3)NOTE: PLEASE NOTE THAT THE PANEL |
| | SCHEDULE NEEDS TO SHOW OCP AND ALL WIRE |
| | SIZES, THE NOTE SAYS #12 AND 20A OCP, |
| | WHAT ABOUT RANGE? DRYER? |
| | |
| | 4)NOTE: PLEASE NOTE PLANS SHOW A WATER |
| | HEATER, PLEASE CLARIFY IF GAS OR ELEC? |
| | IF ELEC, PLEASE LIST. |
| | |
| | 5)NOTE: PLEASE NOTE, PLANS STILL MISSING |
| | FRONT AND REAR RECEPT, 210-52E |
| | |
| | 6)NOTE: PLEASE NOTE THAT GROUNDING |
| | ELECTRODE SYSTEM NEEDS TO BE SHOWN ON |
| | RISER DIAGRAM ALSO. SHOW GROUNDING |
| | ELECTRODE SIZE PER 250-66 AND SHOW |
| | ELECTRODE SYSTEM PER 250-50 TO INCLUDE |
| | COLD WATER PIPE AND GAS BOND IF ANY. |
| | |
| | 7)NOTE: PLEASE NOTE, OUTLET SPACING IS |
| | MISSING SOME OUTLETS REQ`D PER 210-52. |
| | BEDROOMS 1&2 AND KITCHEN. |
| | |
| | 8)NOTE: PLEASE CLARFIY OUTLET SPACING |
| | FOR KITCHEN COUNTER. PLANS SHOW OUTLET |
| | ON WALL AT KITCHEN PENINSULAR, PLEASE |
| | CLARFIY. 210-52-C-1 |
| | |
| | 9)NOTE: PLEASE NOTE THAT SMOKE DETECTORS |
| | CAN NOT BE INSTALLED IN KITCHENS, OR |
| | BATHS PER NFPA-72 2-5.2.1.6 |
| | |
| | 10)NOTE: PLEASE CLARIFY "TWO" SMALL APPL |
| | CIRCUITS. 210-52B |
| | |
| | 11)NOTE: PLEASE SUBMIT TWO COPIES OF |
| | PLANS FOR REVIEW. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |