Plan Review Notes
Plan Review Notes For Permit 01120203
Permit Number 01120203
Review Stop E
Sequence Number 1
Notes
Date Text
2001-12-07 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE SUBMITA CONTRACT TO
 VERFIY VALUE FOR COMPLETE SCOPE OF WORK.
 PLEASE NOTE THAT PER PALM BEACH COUNTY
 AND CITY-WIDE ADMINISTRATIVE CODE 104.7.
 5.. VALUE OS TO INCLUDE ALL LABOR AND
 MATERIALS. EVEN OF SOME PART IS OWNER
 SUPPLIED.
  
 2)NOTE: PLEASE NOTE THAT THERE IS NOT
 ENOUGH INFORMATION FOR SERVICE CHANGE.
 PLEASE SUBMIT A RISER DIAGRAM SHOWING
 MORE DETAIL FOR CONDUIT SIZES, WIRE ,
 GROUNDING ETC.215-5
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
  
 5) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 6) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 7) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 8) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.2
 MECHANICAL CODE.
  
  
 9) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 PLEASE CLARIFY ON REAR BEDROOM.#2
  
 10)NOTE: PLEASE NOTE MISSING CIRCUITS
 REQ`D TO BE MIN FOR WASHER/SM APPLIANCE
  
 11)NOTE: PLEASE CLARIFY IF THERE IS ANY
 A/C UNITS?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION AND
 PLEASE SUBMIT TWO COPIES FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved