| Plan Review Notes For Permit 01120136 |
| Permit Number |
01120136 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-11 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT PER ZONING REG | | | A SEPARATE SERVICE IS NOT PERMITTED FOR | | | ZONING OF SF-7(SINGLE FAMLIY) PLEASE | | | NOTE THAT ELECTRICAL FOR DETACHED GARAGE | | | WOULD NEED TO COME FROM EXISTING ELEC | | | SERVICE OR FROM NEW SERVICE MOUNTED ON | | | GARAGE AND BY BACK FEEDING EXISTING | | | HOUSE. | | | | | | 2)NOTE: PLEASE NOTE THAT ALL OUTLETS IN | | | GARAGE NEED TO BE SHOWN AS GFI/GFI | | | PROTECTED PER210-8. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|