Plan Review Notes
Plan Review Notes For Permit 01120102
Permit Number 01120102
Review Stop E
Sequence Number 2
Notes
Date Text
2002-01-02 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEAS ENOTE THAT NO INFORMATION
 WAS SUBMITTED FOR EXISTING SERVICE SIZE?
 PLEASE SHOW SIZE OF EXISITNG, METERCAN
 AND WIRE SERVICE ENTRANCE CONDUCTORS
 NEW LOAD IS SHOWN AT 57AMPS., PLEASE
 CLARIFY LOAD FOR MAIN HOUSE.
 MAIN HOUSE EXISTING SERVICE WAS 150A.
  
 2)NOTE: PLEASE NOTE THAT NO MEANS OF
 DISCONNECT IS SHOWN FOR
 DETACHED BLDG. 225-31. PLEASE NOTE 125A
 PANEL IS SHOWN AS MLO?
  
 3)NOTE: PLEASE NOTE EXISTING GROUNDING
 ELECTRODE SYSTEM IS SHOWN FOR MAIN HOUSE
 BUT NOT FOR DETACHED BLDG? PLEASE
 CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFOAMTION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372