| Plan Review Notes For Permit 01120102 |
| Permit Number |
01120102 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-10 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE CLARFIY TWO SMALL APPLI- | | | ANCE CIRCUITS SHOWN. AS PER ZOING REQ`- | | | -MENTS, KITCHEN NOT PERMITTED. | | | | | | 2)NOTE: PLEASE CLARIFY SIZE OF EXISTING | | | SERVICE ENTRANCE CONDCUTORS. | | | NEW LOADS BEING ADDED NEED CLARIFICATION | | | | | | 3)NOTE: PLEASE NOTE PLANS SHOW TWO NEW | | | MAIN DISC`S ? PLEASE SUBMIT AIC RATINGS | | | FOR ALL NEW EQUIPMENT PER 110-9. | | | | | | 4)NOTE: PLEASE SHOW LOAD ON EXSITING | | | HOUSE NEEDED FOR CLARIFICATION OF | | | EXISTING SERVICE ENTRANCE CONDUCTORS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|