| Plan Review Notes For Permit 01120053 |
| Permit Number |
01120053 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-01-02 00:00:00 | ******************* UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE THAT NOW HEAT PUMP | | | SPEC AND LOAD CALCUALTIONS WERE SUBMITT- | | | -ED BUT WIRING DIAGRAM STILL DOESN'T | | | REFLECT ANY ASSC WIRING. | | | PLEASE NOTE HEAT PUMP AND WIRING/CONDUIT | | | AND WIRE SIZES MUST BE SHOWN ON PLANS. | | | PLEASE ALOS NOTE THAT ALL CHANGES MUST | | | BE DONE BY THE ENGINEER OF RECORD. | | | FS/FAC 471.025. | | | | | | 2)NOTE: PLEASE CLARIFY SERVICE, LOAD | | | CALCS SHOW TWO 100A PANELS? PLEASE | | | CLARIFY HOW THESE TWO PANELS ARE GETTING | | | THEIR FEEDS? ARE THEY COMING FROM A 200A | | | METERCAN AND SERVICE? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANYQUESTIONS, | | | PLEASE CALL. | | | | | | DEWEYPALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|