| 2001-12-04 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) INDICATE ON THE PLANS THE ELEVATION |
| | OF THE FLOOR IN THE EXISTING STRUCTURE |
| | AND IN THE ENCLOSED GARAGE. |
| | |
| | 4) PROVIDE (2) PRODUCT APPROVALS FOR |
| | STORM PANELS THAT ARE REQUIRED ON NEW |
| | WINDOWS IN ENCLOSED GARAGE. |
| | |
| | 5) INDICATE ON THE PLANS IF ENCLOSED |
| | GARAGE IS TO BE HEATED OR COOLED. IF IT |
| | IS, ENERGY CALCULATIONS PER 97 FLORIDA |
| | ENERGY EFFICIENCY CODE ARE REQUIRED. |
| | |
| | 6) SHEET 4 INDICATES R-30 INSULATION IN |
| | THE IN THE SLOPED CEILING. THERE DOES |
| | NOT APPEAR FROM THE DRAWING TO BE ENOUGH |
| | SPACE BETWEEN THE DRYWALL AND SHEATHING |
| | TO INSTALL IT. PLEASE CLARIFY. |
| | |
| | 7) SHEET 4 INDICATES (3) #4 REINFORCING |
| | BARS IN THE FOOTING. THE MINIMUM SIZE IS |
| | #5 BARS PER SSTD 10-97. IS THIS AN |
| | EXISTING CONDITION. PLEASE CLARIFY. |
| | |
| | 8) INDICATE VERTICAL REINFORCEMENT ON |
| | EACH SIDE OF WINDOW WHERE GARAGE DOOR IS |
| | BEING ENCLOSED. MINIMUM (1) #5 PER |
| | SSTD 10-97. |
| | |
| | 9) INDICATE HOW NEW BLOCK WILL BE |
| | ATTACHED TO EXISTING WALLS AT THE SIDES. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |