| Plan Review Notes For Permit 01120030 |
| Permit Number |
01120030 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-01-02 00:00:00 | ******************DENIED**************** | | | | | | 3RD REVIEW | | | | | | WRONG PERMIT ON SUBMITTAL FORM PERMIT | | | FOR HEAT REMOVAL IS 01120030. | | | | | | COMMENTS FROM 2ND REVIEW NOT ADDRESSED: | | | 1. PROVIDE MANUFACTURES INSTALLATION | | | INTRUCTIONS SHOWING ALLOWABLE | | | CLEARANCE OF B VENT. | | | | | | 2. PROVIDE AREA OF EQUIPMENT LOCATION | | | AND TO DEMONSTRATE ADEQUATE | | | COMBUSTION AIR FOR OVEN AS REQUIRED | | | BY MANUFACTURE. | | | | | | SPECIFICATIONS SUBMITTED 12/27/01, DOES | | | NOT SPECIFY TYPE B VENT.DEVELOPED | | | LENGHT FOR VENT?DRAFT DIVERTER | | | INSTALLED STRAIGHT & 18" - 24" ABOVE | | | CONNECTION.NOTE 2 INDICATES WIND CAP | | | MUST BE INSTALLED AT A MINIMUM OF 4 FT | | | ABOVE ANY OBSTRUCTION (24" INDICATED ON | | | PLAN).TEMPERATURE RANGE UP TO 600 | | | DEGREES F. B VENT FLUE TEMP NOT IN | | | EXCESS OF 550 DEGREES. | | | 1997 SGC 605.3.1. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|