2002-01-02 00:00:00******************DENIED****************
  
 3RD REVIEW
  
 WRONG PERMIT ON SUBMITTAL FORM PERMIT
 FOR HEAT REMOVAL IS 01120030.
  
 COMMENTS FROM 2ND REVIEW NOT ADDRESSED:
 1. PROVIDE MANUFACTURES INSTALLATION
 INTRUCTIONS SHOWING ALLOWABLE
 CLEARANCE OF B VENT.
  
 2. PROVIDE AREA OF EQUIPMENT LOCATION
 AND TO DEMONSTRATE ADEQUATE
 COMBUSTION AIR FOR OVEN AS REQUIRED
 BY MANUFACTURE.
  
 SPECIFICATIONS SUBMITTED 12/27/01, DOES
 NOT SPECIFY TYPE B VENT.DEVELOPED
 LENGHT FOR VENT?DRAFT DIVERTER
 INSTALLED STRAIGHT & 18" - 24" ABOVE
 CONNECTION.NOTE 2 INDICATES WIND CAP
 MUST BE INSTALLED AT A MINIMUM OF 4 FT
 ABOVE ANY OBSTRUCTION (24" INDICATED ON
 PLAN).TEMPERATURE RANGE UP TO 600
 DEGREES F. B VENT FLUE TEMP NOT IN
 EXCESS OF 550 DEGREES.
 1997 SGC 605.3.1.
  
  