| Plan Review Notes For Permit 01111249 |
| Permit Number |
01111249 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-06 00:00:00 | 1) WHAT PREVENTS THE HOSE FROM KINKING | | | AFTER IT IS CONNECTED TO THE FIRE | | | DEPARTMENT CONNECTION SINCE THE RISERS | | | WILL BE LOCATED ON THE SIDES OF THE | | | BUILDING. | | | 2) IT WAS NOTED IN THE SPEC BOOKS AND | | | ON THE PLANS THAT CENTRAL BRAND FIRE | | | SPRINKLER HEADS TYPE LF WILL BE USED. | | | LF SPRINKLER HEADS WERE NOTED ON THE | | | VOLUNTARY RECALL LIST FROM CENTRAL, | | | PLEASE SEE WWW.SPRINKLERREPLACEMENT.COM | | | 3) A 2 1/2 FDC CONNECTION WILL BE | | | REQUIRED. | | | 4) PLEASE EXPLAIN WHY THE SPARE | | | SPRINKLER HEADS WILL BE STORED IN THE | | | CLUBHOUSE AS OPPOSED TO THE INDIVIDUAL | | | BUILDINGS. | | | 5) WHAT PREVENTS THE VALVE FROM BEING | | | CLOSED ON THE UNDERGROUND FIRE LINE. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|