| Plan Review Notes For Permit 01111208 |
| Permit Number |
01111208 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-06 00:00:00 | 1) PLEASE INDICATE ON THE PLANS THAT | | | TEMPORARY STANDPIPE(S) ARE REQUIRED WHEN | | | THE BUILDING REACHES THREE STORIES AND | | | FIFTY FEET IN HEIGHT WHILE IT IS UNDER | | | CONSTRUCTION. | | | 2) THE TWO FIRE DEPARTMENT CONNECTIONS | | | MUST BE WITHIN 150 FEET OF A FIRE | | | HYDRANTS. | | | 3) PLEASE REVIEW NFPA 14, 1993 EDITION | | | SECTION 5-3.2 (E) STANDPIPE CONNECTIONS. | | | 4) PLEASE INDICATE ON THE PLANS ANY | | | AREAS OF THE BUILDING THAT ARE NOT | | | SPRINKLERED AND PROVIDE THE APPLICABLE | | | CODE REFERENCE. | | | 5) NO CUT SHEETS PROVIDED ON FIRE | | | SPRINKLER HEADS PLANNED FOR USE. | | | 6) VALUE OF PERMIT INDICATES A VALUE | | | OF 272,000 DOLLARS. PLEASE PROVIDE | | | DOCUMENTATION. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|