Plan Review Notes
Plan Review Notes For Permit 01111187
Permit Number 01111187
Review Stop B
Sequence Number 1
Notes
Date Text
2001-12-20 00:00:00AN OWNER BUILDER PERMIT MAY ONLY BE
 ISSUED TO THE OWNER OF THE PROPERTY.
 ALTERNATIVELY, ONLY A LICENSED
 CONTRACTOR MAY OBTAIN A PERMIT.SEE
 THE ATTACHED EXCERPT FROM FS 468.
  
 THE GABLE END WALL AT THE NORTH SIDE IS
 REQUIRED BY SBC TABLE 600 TO BE ONE
 HOURFIRE RATED.SEE ALSO FOOTNOTE "I"
 TO TABLE 600 REGARDING TEST
 REQUIREMENTS.
  
 SBC 1012.1.6 REQUIRES A LANDING AT THE
 FRENCH DOORS.
  
 SHEET A3 SECTION AT THE WEST WALL, SHOWS
 WOOD STAIRS WITH A RISE TO RUN RATIO
 THAT DOES NOT COMPLY WITH SBC 1007.3.1.
 ALSO, SHEET A2 SHOWS MASONRY STAIRS.
 PLEASE REVISE AS NECESSARY.
  
 SBC 2309.6 REQUIRES THE ATTIC ACCESS TO
 BE A MINIMUM OF 22" X 36".
  
 SBC 2405.2.1 (2) REQUIRES SAFETY GLAZING
 IN THE WINDOW NEAR THE BATHTUB.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY FOR THE CITY, THE
 PERMIT PLANSSTAMPED BY THAT OFFICE AND
 A COPY OF THEPAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.CALL 233-5025
 FOR MORE INFORMATION.
  
 THE NOTICE OF ACCEPTANCE REPORT FOR THE
 WINDOWS, 98-0218.02, IS EXPIRED.