Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-12-05 00:00:001) FIRE ALARM NOTES INDICATES CLASS B
 CIRCUITS. ONLY CLASS A, STYLE D CIRCUITS
 WILL BE PERMITTED.
 2) FIRE ALARM NOTES INDICATES THAT WHEN
 DUCT SMOKE DETECTORS ARE ACTIVATED, THEY
 WILL CAUSE A SUPERVISORY SIGNAL. THEY
 MUST INITIATE AN ALARM.
 3) THE FIRE ALARM NOTES INDICATE
 SECURITY FEATURES. PLEASE BE ADVISED
 THAT LOCKS ON EXIT DOORS MUST COMPLY
 WITH SPECIAL LOCKING ARRANGEMENTS OF
 THE LIFE SAFETY CODE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910