| Plan Review Notes For Permit 01111133 |
| Permit Number |
01111133 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-29 00:00:00 | 1) THE FIRE DEPARTMENT CONNECTION SHOWN | | | ON THE PLANS IS NOT NEEDED AT THIS | | | TIME BECAUSE IT APPEARS THAT IT WILL | | | SERVE NO PURPOSE UNTIL THE FUTURE. | | | 2) FIRE LINE TO BE INSTALLED IN | | | ACCORDANCE WITH NFPA 24. | | | 3) FIRE LINE TO BE PRESSURE TESTED | | | AT 200 LBS. FOR TWO HOURS. | | | 4) PLANS NEED TO BE SIGNED AND SEALED | | | SINCE A TITLE BLOCK APPEARS ON THE | | | PLANS. (ENGINEERING) | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|