| Plan Review Notes For Permit 01111007 |
| Permit Number |
01111007 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-03-13 00:00:00 | ******************* UNSAT ************ | | | MODEL "E". | | | 1)NOTE: PLEASE NOTE OUTLET SPACING FOR | | | KITCHEN COUNTERSPACE. 210-52-C-1 | | | | | | 2)NOTE: PLEASE NOTE MISSING OUTLET | | | SPACING PER 210-52 | | | | | | 3)NOTE: PLEAS ENOTE THAT POOL PANEL IS | | | STILL NOT SHOWN ON PANEL SCHEDULE? | | | PLEASWE NOTE THAT RISER SHOWS POOL PANEL | | | DISC AND POOL PANEL? PLEASE NOTE THAT | | | POOL PANEL DISC IS SHOWN AT THE REAR OF | | | HOUSE? AND POOL PANEL IN GARAGE? | | | PLEASE CORRELATE LOCATIONS. | | | | | | 4)NOTE: PLEASE NOTE THAT RISER SHOWS | | | POOL PANEL BEING FED WITH TWO "HOTS" | | | AND NO NEUTRAL AND NO EQUIPMENT GROUND- | | | -ING CONDUCTOR?? SIZE PER 250-122 | | | | | | 5)NOTE: PLEASE GO OVER LOAD CALCULATIONS | | | PLEASE REDO TO MEET ART220. THE 40% | | | OF LOAD AFTER FIRST 10KW IS LOWER THAN | | | IT SHOULD BE? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|