| 2002-02-13 00:00:00 | ***************** UNSAT ************** |
| | REVIEW FOR MODEL "E" |
| | PLEASE NOTE THAT NOT ALL ITEMS WERE |
| | ADDRESSED FROM FIRST REVIEW. |
| | PLEASE ALSO NOTE THAT OTHER CHANGES |
| | WERE MADE THAT NEED TO BE ADDRESSED ALSO |
| | |
| | |
| | 1) PLEASE NOTE EITHER MISSING EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. |
| | PLEASE NOTE THAT SOME WERE DONE ON SOME |
| | OF THE MODELS BUT NOT ALL. |
| | |
| | 2) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | PLEASE NOTE SOME WERE DONE AND OTHERS?? |
| | MISSING IN MANY LOCATIONS |
| | 3)NOTE: PLEASE NOTE RECEPT IN GARAGE |
| | NEEDS TO BE SHOWN AS GFI PER 210-8 |
| | |
| | 4)NOTE: PLEASE CLARFIY OUTLET SHOWN |
| | UNDER WATER CLOSET? |
| | |
| | 5)NOTE: PLEASE NOTE THAT OUTLET SPACING |
| | IN KITCHEN CHANGED?? SOME OUTLETS SHOWN |
| | AS DOUBLE INSTEAD? DID ADDRESS COMMENT |
| | FOR BEING GFI. |
| | |
| | 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. |
| | FOOTER STEEL. |
| | |
| | 7)NOTE: PLEASE NOTE, DERATING FOR AHU |
| | LOAD IS DOEN TWICE? |
| | PLEASE NOTE THAT LOAD CALCUALTIONS DO |
| | NOT MEET NEC 220. |
| | |
| | 8) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | NOTE SD`S NOT TO BE WITHIN 3' OF BATHS |
| | AND KITCHENS. NFPA-72 2-5.2.1.6 |
| | |
| | 9)NOTE: PLEASE NOTE THAT RISER NOW SHOWS |
| | AN EQUIPMENT GROUNDING CONDUCTOR BETWEEN |
| | METER AND MAIN DISC. THIS IS PARALLELING |
| | THE NEUTRAL? |
| | |
| | 10)NOTE: PLEASE NOTE THAT 30A POOL PANEL |
| | IS SHOWING 3/0`S FEEDING? PLEASE CLARIFY |
| | AND SHOW OCP ON PANEL SCHEDULE WITH |
| | CONDUCTOR SIZE.SHOW POOL PANEL LOCATION. |
| | |
| | 11)NOTE: PLEASE NOTE THAT NOTES ON |
| | RIGHT STILL REFERENCE WRONG NEC FOR |
| | WHATS LISTED. KITCHEN NOT HAS BATH ART? |
| | PLEASE CORRELATE. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |
| | |
| | ***NOTE** |
| | ONLY ONE SET OF "E" PLANS WERE SUBMITTED |
| | PLEASE SUBMIT TWO FOR PERMITTING. |