| Plan Review Notes For Permit 01111007 |
| Permit Number |
01111007 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-07 00:00:00 | DENIED | | | REFERENCE: SPC-94-SBC-97 | | | | | | 1) BATH #3 DRY HORIZONTAL VENT NOT | | | ALLOWED PER SPC SEC 906.2.1 | | | 2) 3" VENT NOT ALLOWED TO PASS THRU | | | BLOCK WALL AND TIE BEAM PER SBC SEC | | | 1907.3.5 | | | 3) MASTER BATH VENT SEE COMMENT #2. | | | 4) DISHWASHER TO DRAIN INTO GARBAGE DISP | | | OR KITCHEN SINK TAILPIECE. | | | 5) BATH #2 TUB NOT VENTED PROPERLY PER | | | SPC SEC 913.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|