| 2002-03-13 00:00:00 | **************** UNSAT **************** |
| | |
| | MODEL "D" |
| | |
| | 1)NOTE: PLEASE NOTE OUTLET SPACING FOR |
| | KITCHEN COUNTERSPACE PER 210-52-C1. |
| | |
| | 2)NOTE: PLEASE NOTE OUTLET SPACING FOR |
| | WALL SPACES. 2'6'12' RULE. 210-52 |
| | |
| | 3)NOTE: PLEASE NOTE POOL PANEL IS STILL |
| | NOT SHOWN ON MAIN PANEL SCHEUDLE? |
| | PLEASE NOTE THAT RISER SHOWS POOL PANEL |
| | DISC AND AND POOL PANEL? |
| | PLEASE ALSO NOTE THAT PLANS SHOWS THE |
| | POOL PANEL DISC AT THE REAR OF HOUSE |
| | AND POOL PANEL IN GARAGE?? PLEASE |
| | CORRELATE. |
| | |
| | 4)NOTE: PLEASE NOTE THAT RISER DIAGRAM |
| | SHOWS POOL PANEL WITH TWO "HOTS"!, NO, |
| | NEUTRAL , NO EQUIPMENT GROUNDING |
| | CONDUCTOR. ??? |
| | |
| | 5)NOTE: PLEASE GO OVER LOAD CALCUALTIONS |
| | , PLEASE REDO TO MEET 220. THE 40% OF |
| | LOAD AFTER FIRST 10KW IS LOWER THAN IT |
| | SHOULD BE? |
| | |
| | 6)NOTE: PLEASE NOTE THAT SMOKE DETECTORS |
| | ARE REQUIRED INSIDE AND OUTSIDE ALL |
| | BEDRROMS. PLEASE NOTE MISSING SD`S FOR |
| | IN/OUT MASTER BEDROOM. NFPA-72 2-2.1.1.1 |
| | |
| | 7)NOTE: PLEASE NOTE MISSING EGRESS |
| | LIGHTING FROM ATRIUM TO OUTSIDE.210-70 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. PLEASE CALL IF A MEETING IS |
| | NEEDED. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |