| 2002-02-13 00:00:00 | ***************** UNSAT *************** |
| | REVIEW FOR MODEL "D" |
| | PLEASE NOTE THAT NOT ALL NOTES FROM |
| | FIRST REVIEW WERE ADDRESSED AND THEN |
| | OTHER CHANGES WERE MADE. |
| | |
| | 1) PLEASE NOTE EITHER MISSING EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. |
| | PLEASE NOTE THAT SOME LOCATIONS WERE |
| | DONE AND OTHER NOT? |
| | |
| | 2) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | PLEASE NOTE STILL MISSING IN LOCATIONS |
| | |
| | |
| | 3)NOTE: PLEASE NOTE AS CHANGES WERE |
| | MADE TO SHOW KITCHEN COUNTERTOPAS |
| | GFI`S, LOCATION WERE MOVED AND NOW DO |
| | NOT MEET 210-52-C1 PLEASE ALSO NOTE |
| | ISLAND REQ`S ADDITIONAL PER 210-52-C3 |
| | ` |
| | 4)NOTE: PLEASE NOTE THAT ALL OTHER |
| | MODELS SHOW AN ATTIC ACCESS IN GARAGE |
| | OR OTHER? PLEASE NOTE 210-70 IF THIS |
| | MODEL ACCESS. |
| | |
| | 5)NOTE: PLEASE NOTE THAT NOTES ON RIGHT |
| | STILL SHOW WRONG CODE REFERENCE FOR |
| | KITCHEN. SHOWS ART FOR BATHS? |
| | |
| | 6)NOTE: PLEASE NOTE, LOAD CALCULATIONS |
| | NEED TO MEET 220. DERATING IS DONE |
| | TWICE FOR AHU LOAD. AND FINAL KW RATING |
| | IS DIVIDED BY 120VOLTS ON A 230/240 V |
| | SERVICE. PLEASE CORRECT. |
| | |
| | 7) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. |
| | |
| | 8)NOTE: PLEASE NOTE THAT PLANS NOW SHOW |
| | AN EQUIPMENT GROUNDING CONDUCTOR BETWEEN |
| | FIRST MEANS OF DISC AND MAIN? PLEASE |
| | NOTE THAT THIS IS PARALLELING THE |
| | NEUTRAL? |
| | |
| | 9)NOTE: PLEASE NOTE THAT RISER SHOWS |
| | 3/0`S GOING TO 30 POOL PANEL? |
| | PLEASE SHOW OCP AND WIRE SIZE FOR POOL |
| | PANEL. PLEASE SHOW PANEL LOCATION ON |
| | PLANS. |
| | |
| | 10)NOTE: PLEASE NOTE RECEPT ON GARAGE |
| | NEEDS TO GFI PER 210-8. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |