| 2001-12-20 00:00:00 | ************** UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT SEPARATE PLANS |
| | NEED TO BE SUBMITTED FOR EACH SFR. |
| | |
| | 2)NOTE: PLEASE NOTE LOAD SHOWN FOR MAIN |
| | PANEL IS SHOWN ABOVE 200AMPS. |
| | |
| | 3)NOTE: PLEASE NOTE OCP FOR WATER HEATER |
| | NEEDS TO BE AT 125% PER 422-13. |
| | PLEASE CORRELATE OCP WITH WIRE SIZE. |
| | |
| | 4)NOTE: PLEASE NOTE MISSING EGRESS LIGHT |
| | -ING IN MANY LOCATIONS, SOME AREAS SHOWN |
| | WITH OPT LTS WHERE LTS ARE REQ`D 210-70 |
| | HALLS, OUTSIDE ETC. |
| | |
| | 5)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | A/C COND UNIT. 309-2 MECH CODE. |
| | |
| | 6)NOTE: PLEASE NOTE THAT PLANS NEED TO S |
| | SHOW MAIN DICSA NEXT TO METER AS SHOWN |
| | ON RISER DIAGRAM. |
| | |
| | 7) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | PLEASE NOTE THAT NOTES NEED TO SHOW THE |
| | CORRECT ART # IF SHOWN. SHOWN AS 210-52D |
| | WHICH OS FOR BATHS? |
| | |
| | 8)NOTE:PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | PLEASE NOTE PLANS SHOW 210-52D AND |
| | AND COMES FROM 210-11-C-3 |
| | AS LONG AS THIS IS LISTED ON PANEL |
| | SCHEUDULE THEN NOT REQ`D ON NOTES. |
| | |
| | 9)NOTE: PLEASE CLARIFY MISSING EQUIPMENT |
| | GROUNDING COND PER 2505-122 FROM POOL |
| | PANEL TO MAIN PANEL. |
| | |
| | 10)NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR] |
| | REVIEW. IF THERE ARE NAY QUESTIONS, |
| | PLEASE CALL. |
| | |