| Plan Review Notes For Permit 01111005 |
| Permit Number |
01111005 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-03-13 00:00:00 | ************** UNSAT ***************** | | | MODEL "C". | | | 1) NOTE: PLEASE NOTE THAT OUTLET SPACING | | | NEEDS TO MEET 210-52. 2` AND 6` RULE. | | | | | | 2)NOTE: PLEASE NOTE LOAD CALCULATIONS | | | NEED TO BE GONE OVER. PLEASE NOTE THAT | | | AFTER THE FIRST 10KW WASA TAKEN, 40% | | | OF REMAINING, SEEMS TO HAVE COME OUT | | | TOO LOW. | | | PLEASE ADJUST. | | | | | | 3)NOTE: PLEASE NOTE POOL PANEL IS STILL | | | NOT LISTED ON MAIN PANEL SCHEDULE?? | | | PLEASE NOTE THAT RISER SHOWS A POOL | | | PANEL DISC AND POOL PANEL? | | | PLEASE ALSO NOTE THAT POOL PANEL IS IN | | | GARAGE AND POOL PANEL DISC IS SHOWN AT | | | THE REAR OF HOUSE?? PLEASE CORRELATE. | | | | | | 4)NOTE: PLEASE NOTE FEED TO POOL PANEL | | | SHOWING TWO "HOTS"? NO NEUTRAL, NO | | | EQUIPMENT GROUNDING CONDUCTOR?? | | | PLEASE CORRECT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS. | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|