| 2002-02-13 00:00:00 | ****************** UNSAT *************** |
| | |
| | REVIEW FOR MODEL "C" |
| | |
| | PLEASE NOTE THAT NOT ALL NOTES FROM |
| | FIRST REVIEW WERE ADDRESSED. |
| | PLEASE NOTE THAT OTHER CHANGES WERE |
| | MADE THAT NOW NEED TO BE ADDRESSED. |
| | |
| | 1) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | MISSING FIRST FLOOR. |
| | |
| | 2) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | MISSING IN SOME LOCATIONS. |
| | |
| | 3)NOTE: PLEASE NOTE MISSING REQ`D EGRESS |
| | LIGHTING AT MANY LOCATIONS. PER 210-70 |
| | |
| | 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. |
| | FOOTER STEEL. |
| | |
| | 5) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.2 |
| | MECHANICAL CODE. |
| | |
| | 6)NOTE: PLEASE NOTE THAT OUTLET SPACING |
| | ALONG KITCHEN COUNTERSPACES SEEM TO |
| | HAVE CHANGED WHEN "GFI" WAS ADDED? |
| | PLEASE CLARFIY "TWO" OUTLETS SHOWN |
| | TOGETHER. SHOWN ON OTHER MODELS LIKE |
| | THIS. 210-52-C1 |
| | |
| | 7)NOTE: PLEASE NOTE THAT NOTES ON RIGHT |
| | STILL REFERENCE ART FOR BATHS WHEN NOTED |
| | FOR KITCHEN? PLEASE CORRELATE. 210-11-C- |
| | 1. NOTED AS 210-52D"BATHS". |
| | |
| | 8)NOTE: PLEASE NOTE THAT DERATING FOR |
| | AHU WAS TAKEN TWICE AT 65%?? PLEASE |
| | CORRECT. 220 |
| | |
| | 9)NOTE: PLEASE NOTE LOAD CALCULATIONS |
| | NEED TO MEET 220. PLEASE NOTE THAT LOAD |
| | IS SHOWN AS BEING DIVIDED BY 120V ON |
| | A 230/240V SERVICE? PLEASE CLARIFY. |
| | |
| | 10)NOTE: PLEASE NOTE RISER DIAGRAM WAS |
| | REVISED AND NOW SHOWS AN EQUIPMENT |
| | GROUNDING CONDUCTOR BETWEEN METER AND |
| | MAIN DISCONNECT? PLEASE NOTE THAT THIS |
| | IS PARALLELING THE NEUTRAL? |
| | |
| | 11)NOTE: PLEASE NOTE MISSING HALL OUTLET |
| | UPSTAIRS PER 210-52H |
| | |
| | 12)NOTE: PLEASE NOTE THAT RISER SHOWS |
| | 3/0`S GOING TO A 30A POOL PANEL? PLEASE |
| | SHOW PANEL ON PLANS AND SHOW OCP AND |
| | CONDUCTOR SIZE FOR POOL PANEL ON MAIN |
| | PANEL SCHEDULE. |
| | |
| | 13)NOTE: PLEASE NOTE MISSING REQ`D BATH |
| | GFI FOR POWDER ROOM FIRST FLLOR.210-52D |
| | |
| | 14)NOTE: PLEASE NOTE THAT NO OUTLET IS |
| | SHOWING FOR RANGE. ALSO NOT SHOWN ON |
| | OTHER PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |