| Plan Review Notes For Permit 01111002 |
| Permit Number |
01111002 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-02-13 00:00:00 | DENIED | | | REFERENCE: SPC-94 | | | | | | 1) SHT A-02 PLUMBING RISER DIAGRAM DOES | | | NOT MATCH FLOOR PLAN. BATH #2 SHOWS VTR | | | ON FLOOR PLAN BUT NOT ON RISER. | | | 2) SHT A-02 RISER DIA. TUB BATH #2 NOT | | | VENTED | | | 3) SHT A-02 LAVS IN M/BATH "S" TRAPPED, | | | SED 1001.5.2 | | | 4) SHT A-02 TUB NOT VENTED ON FLOOR PLAN | | | AND SHOWS A HORIZONTAL DRY VENT ON RISER | | | SPC SEC 906.2.1. | | | 5) SHT A-02 RISER DIAGRAM, LAUNDRY SINK | | | NOT VENTED AND W/M SHOWS TRAP UNDER- | | | GROUND. IS W/M TRAP GOING TO BE U/G? | | | 6) SHT A-02 DISHWASHER NOT TRAPPED ON | | | RISER. D/W SHOULD DRAIN TO GARBAGE DISP. | | | OR TAILPIECE AT KITCHEN SINK. | | | 7) SHT A-02 RISER DIA. TRAPS FOR KITCHEN | | | SINK ARE UNDERGROUND. PLEASE SHOW TRAPS | | | ON STACK ABOVE GROUND. | | | 8) SHT A-02 MASTER BATH HORIZONTAL DRY | | | VENT NOT ALLOWED. SEC 906.2.1. 3" DOUBLE | | | LAV NOT VENTED PROPERLY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|