| 2002-02-13 00:00:00 | *************** UNSAT **************** |
| | |
| | REVIEW FOR MODEL "B" |
| | |
| | PLEASE NOTE THAT SOME NOTES WERE ADDRESS |
| | -ED AND OTHER NOT. PLEASE NOTE OTHER |
| | CHANGES WERE MADE AND NOW HAVE COMMENTS |
| | TO BE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE NOTE THAT SOME REQ`D |
| | EGRESS LIGHTING WAS STILL NOT ADDRESSED. |
| | 210-70 SOME SHOWN AS OPT?? MISSING OTHER |
| | -S |
| | 2) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | MISSING IN SOME LOCATIONS. |
| | |
| | 3)NOTE: PLEASE NOTE GARAGE OUTLET NEEDS |
| | TO BE SHOWN AS GFI. PER 210-8 |
| | |
| | 4)NOTE: PLEASE NOTE MISSINGLT FOR |
| | ATTIC ACCESSIN BEDROOM CLOSET. 210-70 |
| | |
| | 5)NOTE: PLEASE NOTE, LOAD CALCUALTIONS |
| | NEED TO BE SHOWN PER 220. PLEASE NOTE |
| | DERATING OF AHU TWICE? AT 65% |
| | PLEASE NOTE TOTAL KW DIVIDED BY 120V |
| | ON A 230/240V SERVICE? |
| | |
| | 6)NOTE: PLEASE NOTE THAT RISER SHOWS |
| | 3/0`S TO 30A POOL PANEL? PLEASE SHOW |
| | OCP AND CONDUCTOR SIZES ON PANEL SCHED- |
| | -ULE. PLEASE ALSO SHOW POOL PANEL ON |
| | PLANS. |
| | |
| | 7)NOTE: PLEASE NOTE RISER NOW SHOWS AN |
| | EQUIPMENT GROUNDING CONDUCTOR FROM METER |
| | TO MAIN DISC? PLEASE NOTE THAT THIS IS |
| | PARALLELING THE NEUTRAL. |
| | |
| | 8) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50./FOOTER STEEL. |
| | |
| | 9)NOTE: PLEASE NOTE PLANS STILL SHOW |
| | NOTE ON RIGHT THAT REFERENCES WRONG NEC |
| | ART FOR KITCHEN? PLEASE SEE 210-11-C-1 |
| | NOT 210-52D(BATHS) |
| | |
| | 10)NOTE: PLEASE NOTE MISSING HALLWAY |
| | OUTLET PER 210-52H |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |