| 2002-01-14 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE |
| | SBC*= STANDARD BUILD'G CODE (AMENDMENTS) |
| | FL ENERGY CODE = FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILD'G CONSTR'N |
| | |
| | **NOTE** |
| | MODELS B,C,D AND E HAVE BEEN REVIEWED |
| | UNDER THE STANDARD BUILDING CODE, ANY |
| | PERMIT APPLICATIONS, FOR THESE MODELS, |
| | RECEIVED ON OR AFTER MARCH 1, 2002 WILL |
| | BE REVIEWED UNDER THE FLORIDA BUILDING |
| | CODE 2001. |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SBC* 104.2.1&3ALL MODELS. SUBMITTED |
| | PLANS THAT INCLUDE AN ARCHITECT/ENGINEER |
| | TITLE BLOCK SHALL INCORPORATE AN |
| | EMBOSSED SEAL, DATE AND WET SIGNATURE OF |
| | THE DESIGNER (471.025 AND 481.221 F.S.) |
| | |
| | 4) SBC* 1804.2ALL MODELS.SUBMIT A |
| | SOIL TEST REPORT. |
| | |
| | 5) SHEET A10 GENERAL DETAILS. THIS SHEET |
| | NUMBER/TITLE COMBINATION IS USED FOR TWO |
| | SEPARATE SHEETS CONTAINING DIFFERENT |
| | DETAILS.THE TITLE/NUMBER SHALL BE |
| | AMENDED TO DIFFERENTIATE BETWEEN SHEETS |
| | |
| | 6) SBC 705.1.3OPENING PROTECTIVES. |
| | TABLE 600 REQUIRES THE GLASS BLOCK |
| | WINDOWS ON 'COMMON PROPERTY LINES' TO BE |
| | HAVE 1 HOUR FIRE RESISTANCE RATING. |
| | SUBMIT ADDITIONAL INFORMATION TO JUSTIFY |
| | THE PROPOSED GLASS BLOCKS. |
| | |
| | 7) SBC* 104.2.2MODEL B. THE ELEVATIONS |
| | SHALL INCLUDE VIEWS OF THE WINDOWS OVER- |
| | LOOKING THE ATRIUM. |
| | |
| | 8) SBC 1005.4.4MODEL B.THE MINIMUM |
| | CLEAR WIDTH OF AN EMERGENCY EGRESS |
| | WINDOW IS 20".ON SHEET A-03, FLOOR |
| | LAYOUT, THE BED 2 WINDOW (TYPE D) TO THE |
| | ATRIUM IS SHOWN ON THE WINDOW SCHEDULE |
| | AS 62" WIDE.THIS IS TOO WIDE TO BE |
| | ACCOMMODATED IN THIS LENGTH OF WALL. |
| | REVISE TO DEMONSTRATE COMPLIANCE. |
| | |
| | 9) SBC* 1005.4.2MODELS B AND D.THE |
| | ATRIUM GATE MUST ALLOW EMERGENCY ESCAPE, |
| | FROM BED 2, WITHOUT THE USE OF SEPARATE |
| | TOOLS OR KEYS.THE DOOR TYPE ELEVATION |
| | DOES NOT APPEAR TO SHOW THE SPECIFIED |
| | TYPE E DOOR AS BEING A GATE.AMEND THE |
| | DOOR SCHEDULE AS APPROPRIATE. |
| | |
| | 10) MODEL B.SHEET A-06, ELEVATIONS, |
| | SHOWS A KITCHEN WINDOW AND LIVING ROOM |
| | PATIO DOORS THAT ARE NOT SHOWN ON THE |
| | FLOOR PLAN (SHEET A-03).SHOW CORRECT |
| | ARRANGEMENT. |
| | |
| | 11) MODELS B AND C.WINDOWS AND |
| | EXTERIOR DOORS.SOME OF THE REFERENCES |
| | SHOWN ON THE ELEVATIONS DO NOT CORRELATE |
| | TO THOSE ON THE FLOOR PLANS AND/OR THE |
| | DOOR/WINDOW SCHEDULES. CORRECT THOSE |
| | REFERENCES CONCERNED, INCLUDING, BUT NOT |
| | LIMITED TO, MODEL B ATRUIM GATE, LIVING |
| | ROOM WINDOW, FAMILY ROOM PATIO DOOR AND |
| | FAMILY ROOM WINDOW, AND MODEL C MASTER |
| | BED WALK-IN CLOSET WINDOW.ALSO, THE |
| | MODEL B DOOR TYPE ELEVATION FOR THE |
| | ATRIUM GATE DOES NOT CORRELATE TO THE |
| | FLOOR PLAN OR LEFT ELEVATION. |
| | |
| | 12) PROVISO:PRODUCT APPROVAL (ACCEPT- |
| | ANCE NO 99-1110.04) FOR SERIES 6000 |
| | ALUMINUM FIXED WINDOW.DRAWING NO 548, |
| | SHEET 2 OF 4 IS MISSING. |
| | |
| | 13) PRODUCT APPROVALS.SUBMIT PRODUCT |
| | APPROVALS APPLICABLE TO EACH OF THE |
| | PROPOSED WINDOW AND EXTERIOR DOOR TYPES. |
| | THE MISSING PRODUCT APPROVALS INCLUDE, |
| | AMONG OTHERS, THE WOOD ENTRANCE DOORS |
| | AND THE HORIZONTAL SLIDING WINDOWS. |
| | |
| | 14) ACCORDING TO THE DOOR SCHEDULES THE |
| | SUBMITTED PRODUCT APPROVAL (ACCEPTANCE |
| | NO 99-0311.01) FOR THE 'CONSTRUCTION |
| | SERIES FLUSH OUTSWING RESIDENTIAL STEEL |
| | DOOR-IMPACT' IS NOT APPLICABLE TO MODEL |
| | B, C, D OR E. |
| | |
| | 15) THE SUBMITTED ROOF TILE PRODUCT |
| | APPROVAL FOR INTERLOCKING ROLL CONCRETE |
| | TILES DOES NOT CORRELATE TO THE |
| | ELEVATIONS WHICH SHOW "SPANISH S CEMENT |
| | TILE".SUBMIT AN APPROPRIATE PRODUCT |
| | APPROVAL. |
| | |
| | 16) SBC 1606.2SPECIFY ROOF TILE |
| | FASTENINGS. |
| | |
| | 17) MODEL B.ROOF TRUSS SHOP DRAWING |
| | 01448 SHOWS A NARROW ROOF ARRANGEMENT |
| | OVER THE ENTRANCE FOYER THAT DOES NOT |
| | REFLECT THE ROOF ARRANGEMENT SHOWN ON |
| | THE ROOF FRAMING PLAN AND ELEVATIONS. |
| | |
| | 18) ALL MODELS.TRUSS ANCHOR SCHEDULE. |
| | USP RT161T IS NOT A VALID USP REFERENCE. |
| | SIMPSON MTT27B IS NOT A VALID REFERENCE. |
| | SPECIFY FULL REFERENCE OF USP NFM. |
| | |
| | 19) SHEET A-05, ROOF FRAMING PLAN.THE |
| | BEAM SCHEDULE DOES NOT GIVE DETAILS OF |
| | PATIO BEAMS REF 8F161B.REVISE TO SHOW |
| | BEAM TYPE. |
| | |
| | 20) SBC 2309.7ALL MODELS.CROSS |
| | VENTILATION SHALL BE PROVIDED FOR EACH |
| | SEPERATE ATTIC SPACE.AT LEAST 50% OF |
| | THE REQUIRED VENTILATION AREA SHALL BE |
| | AT A LEVEL NO LESS THAN 3FT ABOVE THE |
| | EAVES VENTS. |
| | |
| | 21) SBC 2405.1MODELS B,C,D AND E.THE |
| | GLASS IN THE MASTER BED SHOWER DOOR AND |
| | WALLS SHALL BE SAFETY GLASS IN |
| | COMPLIANCE WITH THE CONSUMER PRODUCT |
| | SAFETY COMMISSION 16-CODE OF FEDERAL |
| | REGULATIONS, PART 1201 (CPSC 16-CFR, |
| | PART 1201) |
| | |
| | 22) FL ENERGY CODE 103.1.2THE |
| | ARCHITECT, OWNER OR HIS/HER LEGALLY |
| | DESIGNATED AGENT SHALL SIGN THE ENERGY |
| | CODE COMPLIANCE CERTIFICATE. |
| | |
| | 23) FL ENERGY CODE 603.1.ABC.1 |
| | MODELS B, C, D AND E.THE GARAGE DOOR |
| | FALLS WITHIN THE DEFINITION OF AN |
| | 'ADJACENT' DOOR (SECT. 202 DEFINITIONS) |
| | AND SHALL BE SOLID CORE OR INSULATED. |
| | THE DOOR SCHEDULE REFERENCE MARK GIVEN |
| | IS '8' WHICH IS SHOWN AS A TYPE F DOOR. |
| | THE DOOR TYPE ELEVATIONS SHOW TYPE F AS |
| | BEING A DOUBLE DOOR.CORRECTION REQ'D. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |