| 2001-12-20 00:00:00 | ************* UNSAT ******************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT SEPARATE PLANS |
| | NEED TO BE SUBMITTED FOR EACH SFH. |
| | |
| | 2)NOTE: PLEASE NOTE LOAD SHOWN FOR MAIN |
| | PANEL ABOVE 200AMPS. MISPRINT FROM |
| | LOAD CALCAULTIONS. |
| | |
| | 3)NOTE: PLEASE NOTE OCP FOR WATER HEATER |
| | AT 125% PER 422-13. CORRELATE OCP W/ |
| | WIRE SIZE. |
| | |
| | 4)NOTE: PLEASE NOTE MISSING EGRESS LIGHT |
| | -ING IN MANY LOCATIONS, PLEASE ALSO NOTE |
| | SOME AREAS(KITCHEN) SHOW LTS AS OPTS. |
| | WHEN REQ`D BY 210-70. OUTSIDE, HALL, |
| | ETC. |
| | |
| | 5)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | A/C COND UNIT PER 309.2 OF THE MECH CODE |
| | |
| | |
| | 6)NOTE: PLEASE NOTE THAT PLANS NEED TO |
| | SHOW MAIN DISC NEXT TO METERCAN AS SHOWN |
| | ON RISER DIAGRAM. |
| | |
| | 7) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | PLEASE NOTE THAT NOTES NEED TO NOTE |
| | CORRECT ART. NOTED AS 210-52D AND THAT |
| | ART IS FOR BATHS. |
| | |
| | 8) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | PLEASE NOTE PLAN NOTES MENTION 210-52-D |
| | SHOULD ALSO READ 210-11-C-3. AS LONG |
| | AS CIRCUIT(S) IS SHOWN ON PANEL SCHEDULE |
| | THEN NOT NESS TO PLACE IN NOTES. |
| | |
| | 9)NOTE: PLEASE CLARIFY MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR BETWEEN MAIN PANEL |
| | AND POOL PANEL./250-122 |
| | |
| | 10)NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | MISSING IN MANY LOCATIONS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |