Plan Review Notes
Plan Review Notes For Permit 01110998
Permit Number 01110998
Review Stop M
Sequence Number 1
Notes
Date Text
2001-12-10 00:00:00******************DENIED****************
  
  
 PLAN SHEET M-1.1 NOTE 2, EXHAUST FOR BLU
 E PRINT ROOM TO BE SCH 40 PVC.THIS IS
 PROHIBITED IN A RETURN AIR PLENUM AS PER
 1997 SMC 609.1.1.
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 2.PLEASE PROVIDE AIR BALANCE SCHEDULE
 SHOWING COMPLIANCE WITH 1997 SMC
 501.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388