| Notes |
| Date |
Text |
| 2001-11-29 00:00:00 | 1) NO INTERIOR FINISH CALSSIFICATION | | | INFORMATION FOR WALLS AND CEILINGS. | | | 2) CARD READERS NOTED ON DOORS USED FOR | | | EXITING. PLEASE EXPLAIN. DOORS USED FOR | | | EXITING THAT POSSESS ANY LOCKING OR | | | SECURITY DEVICES MUST COMPLY WITH | | | "SPECIAL LOCKING ARRANGEMENTS" OF THE | | | LIFE CODE. IS EGRESS POSSIBLE FROM THE | | | TENANT SIDE REGARDLESS OF THE USE OF A | | | CARD. FREE EGRESS OR FAIL SAFE, OR ARE | | | THE DOORS FAIL SECURE. PLEASE PROVIDE | | | MORE INFORMATION. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|