Plan Review Notes
Plan Review Notes For Permit 01110988
Permit Number 01110988
Review Stop R
Sequence Number 5
Notes
Date Text
2002-05-09 00:00:00TRUSS DRAWINGS SECOND CHECKLIST:
 1-TRUSS LAYOUT: REVISE/UPDATE AGAIN.
 NEED SPECIFIC INFORMATION. SBC 1997
 FOR 110MPH AS PER DESIGN CRITERIA
 USED FOR THE BUILDING ARCHITECT.
 ASCE 7-93 AND SBC 1997 CAN'T BE MIXED
 TOGETHER. SEC. 1606.1.2 SBC 1997.
 IF USING ASCE, THEN THE CORRECT ONE IS
 ASCE 7-95 FOR 140 MPH.
 2-UPDATE AND PROVIDE LEGIBLE AND CLEAR
 GENERAL TRUSS DETAILS AND SPECS
 ACCORDING TO THE CODE USED.
 3-CLARIFY WHY THERE ARE TWO ENGINEERS
 ON GENERAL TRUSS DETAILS. WHO IS THE
 ONE WHO PREPARED THE DETAILS? CHECK
 CHAPTER 471 FLORIDA STATUTES FOR
 ENGINEER'S RESPONSIBILITIES.
 SAME APPLIES FOR TRUSS LAYOUT.
 4-REVISE ENGINEERED TRUSS DRAWINGS:
 A)CODE USED TO BE SPECIFIC INCLUDING THE
 YEAR. EG: SBC 1997.
 B)DESIGN CRITERIA ON MIDDLE OF PAGE SAYS
 SBC/ANSI95 WHILE NOTES AT THE BOTTOM
 OF PAGE SAYS ASCE 7-93. SBC AND ASCE
 CAN'T BE MIXED TOGETHER (SEC 1606.1.2.
 SBC 1997). BESIDES, THE RIGHT ASCE IS
 ASCE 7-95 FOR 140MPH.
 C)NOTE THAT SAYS THAT THIS TRUSSES
 COMPLIES WITH FLORIDA BUILDING CODE IS
 NOT TRUE. REVIEW FBC 2001. BESIDES
 FBC 2001 USES ASCE 7-98.
  
 5-ARCHITECT TO PROVIDE A CLEAR ANCHOR
 SCHEDULE WITH CONNECTORS THAT RESIST
 THE UPLIFT & LATERAL LOADS CALCULATED
 ON ENGINEERED TRUSSES. SOME CONNECTORS
 DON'T MEET SUCH LOADS. REVIEW TRUSSES.
 **NOTE: ANCHOR SCHEDULE CALLS FOR USP
 ETA CONNECTORS. WHAT PAGE ON THE USP
 CATALOGUE ARE THESE CONNECTORS LISTED?
 I LOOKED THROUGHT CATALOGUE AND WAS
 NOT ABLE TO FIND IT.
 6-RE-SUBMITTAL FEES WILL BE APPLIED
 WHEN RESUBMITTING TRUSSES FOR MULTIPLE
 REVIEWS. SEE ATTACHED COPY FOR
 RE-SUBMITTAL FEES.