Plan Review Notes
Plan Review Notes For Permit 01110988
Permit Number 01110988
Review Stop R
Sequence Number 2
Notes
Date Text
2002-02-07 00:00:00APPROVED WITH PROVISO:
 1-SOIL TEST REPORT TO HAVE ORIGINAL SEAL
 SIGNATURE AND DATE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORD
 2-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 3-PROVIDE AT LEAST ONE BATHROOM WITH A
 DOOR THAT ALLOWS AT LEAST 29" CLEAR
 OPENING (POWDER RM DOESN'T QUALIFY).
 4-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS (ONE SUBMITTED EXPIRED).
 B)GLASS BLOCK WITH LEGIBLE DRAWINGS.
 C)BUTT GLAZING ASSEMBLY AS SHOWN ON
 PLANS. IF PRODUCT APPROVAL IS NOT
 AVAILABLE, THEN PROVIDE COMPLETE
 ENGINEERING & SPECIFICATIONS FOR SITE
 SPECIFIC INSTALLATION AND USE ATTACHED
 SAMPLE FORM. THIS FORM TO BE SIGNED,
 SEALED AND DATED BY THE MANUFACTURER'S
 ENGINEER AND BY THE ARCHITECT OF
 RECORD.
 D)BBQ UL LISTING.
 E)FIXED WINDOWS: CLEARLY INDICATE ON
 APPROVED DRAWINGS THE COMPONENTS TO BE
 USED IN THIS PROJECT.
 ALSO, INDICATE WINDOWS TO BE USED
 ACCORDING TO THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT.
 F)HIGH DENSITY FOAM SPECS.
 5-PROVIDE COMPLETE SPECIFICATIONS FOR
 CEILING INSTALLATION AT ENTRY AND REAR
 PORCH. DON'T CITE THE CODE. SEE ASTM
 C926 AND ASTM C1063 AND PROVIDE THE
 REQUIRED SPECIFICATIONS.
 SEC. 104.2.1 CITY AMENDMENTS TO SBC/97
 6-REVISE DETAIL E OF A8 TO MATCH ACTUAL
 CONDITIONS. SEE FRONT ELEVATION.
 7-CLARIFY TRUSS ANCHOR SCHEDULE. WHAT
 CATALOGUE WAS USED TO FIND THE ETA
 CONNECTORS?.
 8-PROVIDE PLANS/DETAILS FOR OPTIONAL
 SHOWER AT POWDER ROOM.
 9-PROVIDE SURVEY WITH BUILDING LAYOUT.