Plan Review Notes
Plan Review Notes For Permit 01110988
Permit Number 01110988
Review Stop E
Sequence Number 1
Notes
Date Text
2001-12-11 00:00:00****************** UNSAT ***********
  
  
 1)NOTE: PLEASE NOTE, MISSING CONDUIT AND
 CONDUCTOR SIZES FROM METER TO MAIN DISC-
 S. PLEASE CLARIFY.
  
 2)NOTE: PLEASE NOTE MISSING GARAGE RECEP
 210-52G AND GFI/ PER 210-8.
  
 3)NOTE: PLEASE NOTE MISSING SMOKE DETECT
 IN BEDROOM #4. PER NFPA-72 2-2.1.1.1
  
 4)NOTE: PLEASE NOTE MISSING OUTLET ON
 KITCHEN COUNTERSPACE AS GFI. PER 210-8-
 A-6.
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICALPLAN REVIEW
 561-659-8096 EXT 8372