| Plan Review Notes For Permit 01110988 |
| Permit Number |
01110988 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-11 00:00:00 | ****************** UNSAT *********** | | | | | | | | | 1)NOTE: PLEASE NOTE, MISSING CONDUIT AND | | | CONDUCTOR SIZES FROM METER TO MAIN DISC- | | | S. PLEASE CLARIFY. | | | | | | 2)NOTE: PLEASE NOTE MISSING GARAGE RECEP | | | 210-52G AND GFI/ PER 210-8. | | | | | | 3)NOTE: PLEASE NOTE MISSING SMOKE DETECT | | | IN BEDROOM #4. PER NFPA-72 2-2.1.1.1 | | | | | | 4)NOTE: PLEASE NOTE MISSING OUTLET ON | | | KITCHEN COUNTERSPACE AS GFI. PER 210-8- | | | A-6. | | | | | | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICALPLAN REVIEW | | | 561-659-8096 EXT 8372 |
|