Plan Review Notes
Plan Review Notes For Permit 01110976
Permit Number 01110976
Review Stop B
Sequence Number 1
Notes
Date Text
2001-12-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC*= STANDARD BUILD'G CODE (AMENDMENTS)
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SBC* 104.1.1A PRODUCT APPROVAL IS
 REQUIRED FOR THE ELECTRICAL ROLL DOWN
 SHUTTERS.
  
 4) SBC 1503.1.2.3THE ROOF SLOPE SHALL
 BE MINIMUM 1/4" PER FOOT.
  
 5) SBC 2308.2.2.1THE PLYWOOD WALL
 SHEATHING SHALL BE MINIMUM 5/8" THICK.
  
 6) SBC 2306.2THE WOOD HEADER DETAIL
 REFERS TO A SIMPSON MSTA16 CONNECTOR
 BETWEEN THE HEADER AND JACK STUD.THIS
 IS NOT A VALID SIMPSON REFERENCE.
 PROVIDE PRODUCT DETAILS OR A CORRECT
 REFERENCE.
  
 7) FL ENERGY CODE 103.0COMPLIANCE WITH
 THE CODE SHALL BE DEMONSTRATED THROUGH
 SUBMITTAL OF CODE COMPLIANCE FORMS.
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499