Date Text
2001-11-30 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.IS THIS A NEW SERVICE OR CHANGEOUT/
 UPGRADE.ENERGY CALCULATIONS ARE
 REQUIRED.
  
 2.PLEASE INDICATE WHAT TYPE OF WOOD
 WORK IS BEING DONE.NO SANDING,
 GRINDING, FINISHING.AS PER NFPA
 90A 2-3.7.1 AIR SHALL NOT BE RE-
 CIRCULATED FROM ANY SPACE IN WHICH
 FLAMMABLE VAPORS, FLYINGS, OR DUST
 IS PRESENT IN QUANTITIESAND
 CONCENTRATIONS THAT WOULD INTRODUCE
 HAZARDOUS CONDITION INTO THE RETURN
 AIR SYSTEM.
  
 3.WHAT IS BEING STORED IN THE STORAGE
 ROOM?SHOW COMPLAINCE WITH 1997
 SMC 501.2 (300 CFM BEING SUPPLIED -
 NO RETURN AIR.
  
 4.DETAIL OF ROOF CURB, ATTACHMENT TO
 JOIST & LOAD CALCS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.