| 2001-12-11 00:00:00 | ****************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT PLANS THAT ARE |
| | SIGNED, DATED AND SEALED BY AN ENGINEER |
| | MUST HAVE A TITLE BLOCK, PER61G15-23.002 |
| | OF FAC/FS. |
| | |
| | 2)NOTE: PLEASE NOTE THAT THE ELECTRICAL |
| | RISER DIAGRAM ON 6OF6 NEEDS TO BE ON THE |
| | ELECTRICAL PLAN. |
| | |
| | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 4) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | |
| | 5) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. |
| | PLEASE NOTE THAT NOTE SAYS GROUND ROD |
| | DRIVEN 6', PLEASE SEE NEC FOR MIN BURIAL |
| | DEPTH. |
| | |
| | 7) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | PLEASE CLARIFY IF IT IS AN OUTLET SHOWN |
| | FOR WALL IN FAMILY ROOM? |
| | |
| | 8) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| | BY 210-52E OF THE NEC. MISSING FRONT REC |
| | |
| | 9) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.2 |
| | MECHANICAL CODE. |
| | |
| | 10)NOTE: PLEASE NOTE MISSING COND UNIT |
| | FOR A/C AND DISC PER 440-11. |
| | |
| | 11)NOTE: PLEASE NOTE OUTLETS SHOWN IN |
| | GARAGE NEED TO BE SHOWN AS GFI/GFI |
| | PROTECTED ALONG WITH ALL OUTSIDE OUTLETS |
| | (BACK PORCH). PER 210-8. |
| | |
| | 12)PLEASE NOTE EITHER MISSING EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. |
| | PLEASE SEE BATHROOM BETWEEN BEDROM 2-3, |
| | PLEASE NOTE TWO RECEPTS SHOWN??? |
| | NO LIGHT OR LIGHT SWITCH. PLEASE CORRECT |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |