| Plan Review Notes For Permit 01110917 |
| Permit Number |
01110917 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-02-04 00:00:00 | DENIED | | | REFERENCE: SPC-94 - SGC-97 - FACBC-97 | | | | | | 1) FROM PREVIOUS REVIEW. - FOLLOWING IN- | | | FORMATION REQUIRED FOR GAS PERMIT. | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER STANDARD | | | GAS CODE. | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER THE STANDARD GAS | | | CODE SECS. 402.4 THRU 402.4.4.7. | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER STANDARD GAS CODE SEC. 305.2. IF | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | STANDARD GAS CODE SEC. 402. | | | -- ALSO A SHUT OFF VALVE AND UNION ARE | | | REQUIRED UPSTREAM OF ALL REGULATORS.- | | | | | | 2) FROM PREVIOUS REVIEW. SHT P.03, WATER | | | PIPING ISOMETRIC, POOL MAKE UP WATER TO | | | HAVE AN AIR GAP, WATTS N36 VACUUM BREAK- | | | ER, OR AN RPZ BACKFLOW. PLUMBER TO PROV- | | | IDE FOR POOL CONTRACTOR. PLEASE PROVIDE | | | DETAILS FOR PROTECTION OF POTABLE WATER. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|