Date Text
2002-02-04 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) FROM PREVIOUS REVIEW. - FOLLOWING IN-
 FORMATION REQUIRED FOR GAS PERMIT.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER THE STANDARD GAS
 CODE SECS. 402.4 THRU 402.4.4.7.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 -- ALSO A SHUT OFF VALVE AND UNION ARE
 REQUIRED UPSTREAM OF ALL REGULATORS.-
  
 2) FROM PREVIOUS REVIEW. SHT P.03, WATER
 PIPING ISOMETRIC, POOL MAKE UP WATER TO
 HAVE AN AIR GAP, WATTS N36 VACUUM BREAK-
 ER, OR AN RPZ BACKFLOW. PLUMBER TO PROV-
 IDE FOR POOL CONTRACTOR. PLEASE PROVIDE
 DETAILS FOR PROTECTION OF POTABLE WATER.
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377