| Plan Review Notes For Permit 01110917 |
| Permit Number |
01110917 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-04 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SEPARATE GAS PERMIT REQUIRED. SEE | | | ATTACHED SHEET FOR PERMIT APPLICATION | | | REQUIREMENTS. PLEASE RESPOND TO #'S 1, | | | 6, 7, & 9. | | | 2) SHT P.03 GAS PIPING ISOMETRIC, TOTAL | | | BTU'S ADD UP TO 6,225,000. 7,225,000 IS | | | SHOW, PLEASE CLAIRFY. | | | 3) SHT P.03, WATER PIPING ISOMETRIC, | | | POOL MAKE UP WATER TO HAVE AN AIR GAP, | | | OR A WATTS N36 VACUUM BREAKER. PLEASE | | | SHOW DETAILS. - ALL WATER HAMMER ARRES- | | | TORS SHALL BE LOCATED IN AN EFFECTIVE | | | RANGE, (CLOSE TO), FIXTURE NOT AT TOP OF | | | DROP AS SHOWN AT POOL MAKE UP WATER. | | | 4) SHT P.01 COLUMN LINE BB/14A, WHAT ARE | | | THE (2) 2" CAPPED LINES FOR? | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|