2001-12-04 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SEPARATE GAS PERMIT REQUIRED. SEE
 ATTACHED SHEET FOR PERMIT APPLICATION
 REQUIREMENTS. PLEASE RESPOND TO #'S 1,
 6, 7, & 9.
 2) SHT P.03 GAS PIPING ISOMETRIC, TOTAL
 BTU'S ADD UP TO 6,225,000. 7,225,000 IS
 SHOW, PLEASE CLAIRFY.
 3) SHT P.03, WATER PIPING ISOMETRIC,
 POOL MAKE UP WATER TO HAVE AN AIR GAP,
 OR A WATTS N36 VACUUM BREAKER. PLEASE
 SHOW DETAILS. - ALL WATER HAMMER ARRES-
 TORS SHALL BE LOCATED IN AN EFFECTIVE
 RANGE, (CLOSE TO), FIXTURE NOT AT TOP OF
 DROP AS SHOWN AT POOL MAKE UP WATER.
 4) SHT P.01 COLUMN LINE BB/14A, WHAT ARE
 THE (2) 2" CAPPED LINES FOR?
  
 REVIEW BY KEN STEVENS