2001-12-10 00:00:00********************DENIED**************
  
  
 CLARIFY WHAT IS BEING SUBMITTED WITH
 THIS PERMIT APPLICATION.
  
 1.MECHANICAL PLANS ARE FOR THE BOILER
 ROOM.PLEASE PROVIDE CALCULATIONS
 FOR COMBUSTION AIR.
  
 2.STORAGE ROOM ADDITION.
  
 A. WHAT IS BEING "STORED" IN THIS
 AREA?
 B. PROVIDE AIR BALANCE SCHEDULE
 SHOWING COMPLIANCE WITH 1997 SMC
 501.2.
  
 3.PLAN SHEET M.03 EF-3, CLARIFY SHAFT,
 DOES THIS HAVE A FIRE RATING?WHAT
 IS THE RATING OF THE WALL SEPARATING
 THE STORAGE AREA FROM THE EXISTING
 BUILDING?
  
 4.BOILER ROOM, WHAT IS THE FIRE
 RATING OF THIS ROOM?PLEASE NOTE
 THERE ARE NO FIRE DAMPERS INDICATED
 ON DUCTS PENETRATING THE WALL
 BETWEEN THE BOILER ROOM AND THE
 EXISTING BUILDING.
  
 IF YOU HAVE ANYQUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.