| 2001-12-05 00:00:00 | ***************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE ADDRESS FIRE COMMENTS |
| | FOR USE OF STORAGE. |
| | |
| | NOTE;PLEASE NEED CLARIFICATION ON THE |
| | FOLLOWING ITEMS. |
| | |
| | 2)NOTE: PLEASE NOTE THAT GENERATOR |
| | ENCLOSURE ON E.01 APPEARS TO BE IN AN |
| | ENCLOSED ROOM??? PLEASE SEE INSIDE |
| | LIGHTING ,EM LT, RECEPT?? PLEASE NOTE |
| | THAT ON SHEET E.02, IT APPEARS TO BE |
| | IN A FENCED IN AREA? PLEASE NOTE THAT |
| | ALL CIRCUITS NEED TO HAVE A MEANS OF |
| | DISCONNECT FOR DETACHED STRUCTURE PER |
| | 225-31. GROUNDING PER 250-32 |
| | |
| | 3)NOTE: PLEASE SHOW GROUNDING OF NEW |
| | TRANSFORMER, 250-30 |
| | |
| | 4)NOTE: PLEASE NOTE THAT SHEET E.01 |
| | SHOWS FEED COMING FROM BRKR ON GEN. AND |
| | SHOWS A CIRCLE W/ "G-1" PLEASE CLARIFY |
| | THIS?? |
| | |
| | 5)NOTE: PLEASE NOTE THAT SHEET C.01 |
| | SHOWS A "NEW" GENERATOR AND E-SHEETS |
| | DO NOT SHOW ANY DETAIL FOR THIS? GEN, |
| | SIZE, WIRING,CONDUITS WHERE,WHAT, LOAD? |
| | ALL EXSITING??? PLEASE CLARFIY. |
| | |
| | 6)NOTE: PLEASE NOTE THAT "DP-1" SHOWN |
| | AS "DIST PANEL"? IS THERE ANY OTHER |
| | LOADS? EXISTING? |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |