Plan Review Notes
Plan Review Notes For Permit 01110917
Permit Number 01110917
Review Stop B
Sequence Number 1
Notes
Date Text
2001-12-20 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC*= STANDARD BUILD'G CODE (AMENDMENTS)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SBC* 104.1.1THE PRIMARY PERMIT
 APPLICATION SHOWS ROOFING AS BEING OFF
 PERMIT.A SEPARATE ROOFING PERMIT IS
 REQUIURED.
  
 4) SBC 704.1.3.3SHEET A.01 FIRST
 FLOOR PLAN SHOWS THE WALL BETWEEN THE
 BOILER ROOM AND NEW STORAGE AREA AS 4 HR
 RATED WITH A REFERENCE TO TYPE B.SHEET
 A.07 WALL SCHEDULE, WHICH REFERS TO
 TYPE B AS NON-RATED, SHOULD THEREFORE BE
 AMENDED TO CONFIRM THE FIRE-RATED
 CONSTRUCTION REQUIREMENT.
  
 5) SBC 1503.1.2.3THE FLAT ROOF SLOPE
 SHALL BE AT LEAST 1/2" PER FOOT.THE
 ROOF LEVELS ON SECTION 1, SHEET A.05
 IMPLY A SHALLOWER SLOPE THAN THIS.
  
 6) FL ACC CODE 4.8OUTDOOR PATIO DECK
 RAMP SHALL HAVE A MAXIMUM SLOPE OF 1:12
 AND A MINIMUM WIDTH OF 36 INCHES.
 ANNOTATE THE PLANS TO SHOW THESE
 REQUIREMENTS.
  
 7) FL ACC CODE 4.8.5THE RAMP SHALL
 HAVE HANDRAILS ON BOTH SIDES WHICH MEET
 THE REQUIREMENTS OF FL ACC CODE 4.8.5
 AND SBC 1608.2.1
  
 8) SBC 1608.2.2SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE WITH THE
 REQUIREMENTS FOR THE DESIGN AND
 CONSTRUCTION OF THE OUTDOOR PATIO DECK
 GUARDRAILS.
  
 9) SBC* 1804.2.2SUBMIT A COPY OF THE
 GEOTECHNICAL REPORT.
  
 10) SBC 1604.3WHAT ITEMS WILL BE
 STORED?IF STORAGE RACKING IS TO BE
 USED, THE FLOOR SLAB SHALL BE CHECKED
 FOR PUNCHING SHEAR UNDER RESULTING
 CONCENTRATED LOAD AT THE RACKING SUPPORT
  
 11) SBC 1606.2STATE THE DESIGN WIND
 PRESSURES AND SUBMIT DETAILS TO DESCRIBE
 THE STRUCTURAL SYSTEM FOR TRANSFER OF
 WIND LOADS TO THE FOUNDATIONS.
  
 12) SBC 1608.1.1SUBMIT DETAILS TO
 DEMONSTRATE THE LATERAL RESTRAINT OF THE
 NEW RETAINING WALL WERE IT INTERSECTS
 WITH THE EXISTING WALL (ADJACENT GRID
 REF CC/17A).
  
 13) PROVISO: FL ENERGY CODE 101.5.3IF
 THE SPACE IS TO BE HEATED OR COOLED BY
 MECHANICAL MEANS, CODE COMPLIANCE SHALL
 BE DEMONSTRATED BY SUBMITTAL OF ENERGY
 CODE COMPLIANCE FORMS (FL ENERGY CODE
 103.0).