| Plan Review Notes For Permit 01110813 |
| Permit Number |
01110813 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-26 00:00:00 | DENIED | | | REFERENCE: SPC-94 | | | | | | 1) ALL PLANS WITH A TITLE BLOCK SHALL BE | | | SIGNED AND SEALED BY ENGINEER OF RECORD | | | PER FS 61G15-23.002 | | | 2) PAGE 1 OF 2 STATES THAT NO PLUMBING | | | INCLUDED WITH THESE PLANS. PLEASE CLAIR- | | | IFY. | | | 3) 2ND FLOOR RISER DIAGRAM NOT TO CODE | | | BATH TUB NOT VENTED PROPERLY PER SPC SEC | | | 913.2 | | | 4) 1ST FLOOR PLAN, WHAT FIXTURE IS BEING | | | DRAINED AT WATER HEATER. MORE INFORMAT- | | | ION REQUIRED. | | | 5) PAGE 1 0F 2, KITCHEN SINK NOT VENTED | | | PROPERLY. | | | 6) PAGE 1 OF 2, FIXTURES NOT IDENTIFIED | | | IN LAUNDRY ROOM. 1ST FIXTURE NOT VENTED | | | PROPERLY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|