| Plan Review Notes For Permit 01110796 |
| Permit Number |
01110796 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-14 00:00:00 | ************BUILDING PROVISO************ | | | | | | 1) STRUCTURE IS LOCATED IN AN A8 FLOOD | | | ZONE, AN ELEVATION CERTIFICATE IS | | | REQUIRED. | | | | | | 2) RESUBMIT STORM PANEL INFORMATION WITH | | | MASTERED DRAWINGS. THE ONES THAT WERE | | | SUBMITTED ARE COPIES OF ENGINEERED | | | DRAWINGS THAT ARE STAMPED VALID FOR ONE | | | PERMIT ONLY. | | | | | | 3) PROVIDE UPDATED PRODUCT APPROVALS FOR | | | FRONT DOOR. | | | | | | 4) SUBMIT CURRENT PRODUCT APPROVAL FOR | | | GARAGE DOOR. SBCCI HAS DELETED THE 2015 | | | REPORT FOR ABLE GARAGE DOORS. | | | | | | 5) REVISE THE TYPICAL EXTERIOR CEILING | | | DETAIL ON A-1,A-1B TO COMPLY WITH | | | ASTM C-1063, WHICH REQUIRES FASTENERS TO | | | PENETRATE INTO HORIZONTAL FRAMING 1-3/4" | | | | | | 6) MASTER BEDROOM WINDOWS MUST COMPLY | | | WITH 97 SBC 1005.4, FOR EMERGENCY ESCAPE | | | AND RESCUE OPENINGS. |
|