2002-01-14 00:00:00************BUILDING PROVISO************
  
 1) STRUCTURE IS LOCATED IN AN A8 FLOOD
 ZONE, AN ELEVATION CERTIFICATE IS
 REQUIRED.
  
 2) RESUBMIT STORM PANEL INFORMATION WITH
 MASTERED DRAWINGS. THE ONES THAT WERE
 SUBMITTED ARE COPIES OF ENGINEERED
 DRAWINGS THAT ARE STAMPED VALID FOR ONE
 PERMIT ONLY.
  
 3) PROVIDE UPDATED PRODUCT APPROVALS FOR
 FRONT DOOR.
  
 4) SUBMIT CURRENT PRODUCT APPROVAL FOR
 GARAGE DOOR. SBCCI HAS DELETED THE 2015
 REPORT FOR ABLE GARAGE DOORS.
  
 5) REVISE THE TYPICAL EXTERIOR CEILING
 DETAIL ON A-1,A-1B TO COMPLY WITH
 ASTM C-1063, WHICH REQUIRES FASTENERS TO
 PENETRATE INTO HORIZONTAL FRAMING 1-3/4"
  
 6) MASTER BEDROOM WINDOWS MUST COMPLY
 WITH 97 SBC 1005.4, FOR EMERGENCY ESCAPE
 AND RESCUE OPENINGS.