Plan Review Notes
Plan Review Notes For Permit 01110795
Permit Number 01110795
Review Stop R
Sequence Number 1
Notes
Date Text
2001-12-20 00:00:00*************BUILDING UNSAT*************
  
 1) THE PRIVACY WALL DETAIL (F-13) ON A-1
 INDICATES FILLED CELLS W/ VERTICLE
 REINFORCEMENT AT 24" O.C. AND THE PLAN
 SHOWS 8"X16" BLOCK W/2 #5 VERTICLE BARS
 SPACED 5' O.C. PLEASE CORRECT.
  
 2) THE WALL SECTION ON A-2 INDICATES A
 20" DEEP FOOTER AND THE FOOTER SCHEDULE
 ON A-1 HAS THE FOOTER DEPTH OF 18".
 PLEASE CORRECT.
  
 3) THE ROOF NOTES ON THE WALL SECTION ON
 A-2 SPECIFIES THE SHEATHING NAILED 4"
 O.C. THRU-OUT THE ENTIRE ROOF AND THE
 STRUCTURAL NOTES ON A-4 CALL FOR THE
 ROOF SHEATHING TO BE NAILED 4" ON THE
 EDGES AND 6" IN THE FIELD. PLEASE
 CORRECT.
  
 4) THE DOOR FROM THE GARAGE TO THE
 CONDITIONED SPACE IS REQUIRED TO BE
 INSULATED OR SOLID CORE PER FLORIDA
 ENERGY EFFICIENCY CODE.
  
 5) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 6) A DESIGN CERTIFICATION FORM IS
 REQUIRED, UNLESS ALL THE INFORMATION
 REQUIRED ON THE FORM IS ON THE PLANS.
 NOT ALL REQUIRED INFORMATION HAS BEEN
 PROVIDED. INDICATE IF BUILDING IS
 DESIGNED AS OPEN,ENCLOSED,ETC. INDICATE
 THE IMPORTANCE FACTOR, BASIC WIND
 VELOCITY, IF REVIEWED FOR SHEAR WALL
 REQUIREMENTS. SEE FORM ATTACHED.
  
 7) HUGHES AND SEMCO HAVE BEEN PURCHASED
 BY USP AND SOME VALUES HAVE CHANGED.
 PLEASE REVIEW TRUSS CONNECTOR SCHEDULE.
  
 8) INDICATE THE SIZE AND LENGTHS OF THE
 TAPCONS AND WOOD SCREWS THAT ARE TO BE
 USED TO ATTACH THE P.T. 2X8S SHOWN ON
 THE DOOR FRAME DETAIL ON A-6.
  
 9) SPECIFY THE SIZE, NUMBER AND LENGTH
 OF THE FASTENERS THAT WILL BE USED WITH
 THE #7 ALTERNATE CONNECTOR SHOWN ON A-6.
 INDICATE THE UPLIFT THAT THIS CONNECTOR
 IS CAPABLE OF RESISTING.
  
 10) INDICATE THE SPACING OF THE DN 72P8
 FASTENERS USED TO ANCHOR THE DOOR BUCKS
 IN THE BUCK DETAIL ON A-6.
  
 11) PROVIDE BUCK DETAILS FOR THE 8 FEET
 WIDE SLIDING GLASS DOORS. THE BUCK
 DETAIL ON A-6 IS FOR SLIDING GLASS DOORS
 UP TO 6' WIDE.
  
 12) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR GLASS BLOCK. PROVIDE
 FIRE RATING INFORMATION FOR GLASS BLOCK.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202