Plan Review Notes
Plan Review Notes For Permit 01110769
Permit Number 01110769
Review Stop R
Sequence Number 1
Notes
Date Text
2001-12-24 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) PROVIDE OVERFLOW SCUPPERS PER 97SBC
 SEC. 1517.6.4.
  
 3) INDICATE THE EXTERIOR WINDOW AND DOOR
 SIZES AND TYPES ON THE PLANS.
  
 4) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ARCHED FIXED GLASS WINDOWS
 - STRUCTURAL MULLIONS
 - SINGLE FRENCH DOOR (THE APPROVAL THAT
 WAS SUBMITTED IS FOR SINGLE UNIT
 APPLICATION OF A PAIR OF DOORS AND A
 SINGLE DOOR WITH SIDELITE ONLY)
 THE FRENCH DOOR PRODUCT APPROVALS WERE
 ALSO MISSING THE APPROVED DRAWINGS.
  
 5) PROVIDE A BATHROOM WITH A DOOR HAVING
 A 29" CLEAR OPENING PER FL ACCESSIBILITY
 CODE.
  
 6) PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 1997 FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
  
 7) PROVIDE PRODUCT APPROVALS FOR ROOFING
 MATERIALS UNDER A SEPARATE PERMIT.
  
 8) INDICATE HOW THE FOYER WALLS WILL BE
 ATTACHED TO THE EXISTING STRUCTURE AND
 NEW BLOCK STRUCTURE.
  
 9) INDICATE THE TRUSS TO DOUBLE PLATE
 AND DOUBLE PLATE TO (3) 2X 10 BEAM
 CONNECTIONS REQUIRED FOR A CONTINOUS
 LOAD PATH.
  
 10) THE ROOF SHEATHING NAILING SPECIFIED
 ON SHEET 4 IS INCORRECT. THE CITY OF WPB
 AMENDMENTS TO THE 97SBC SEC. 2306
 REQUIRE 6"O.C. AT EDGES AND 6" O.C.
 INTERMEDIATE IN ROOF ZONES 1 & 2.
  
 11) INDICATE COMPLIANCE WITH CITY OF WPB
 AMENDMENTS TO 97 SBC SEC. 2304.2.5.
 WHERE LATH AND STUCCO FINISH IS APPLIED
 OVER THE EXTERIOR OF WOOD FRAME
 CONSTRUCTION, AN APPROVED WEEP SCREED
 (STUCCO STOP) PLACED NOT LESS THAN 6"
 ABOVE FINISHED GRADE SHALL BE USED TO
 TERMINATE THE STUCCO AT THE BASE OF THE
 WALL.
  
 12)PROVIDE FIRE BLOCKING AT INTERSECTION
 OF WALL AND CEILING PER 97SBC SEC.2305.1
  
 13) PROVIDE FIRECUTS WHERE TRUSSES
 TERMINATE IN MASONRY WALLS PER 97 SBC
 SEC. 2305.4.
  
 14) INDICATE WALL FURRING MATERIAL THAT
 WILL BE USED ON WALL SECTION.
  
 15) INDICATE ATTIC VENTILATION AS
 REQUIRED BY 97 SBC SEC. 2309.7.
  
 16) PROVIDE ARCHITECT'S TITLE BLOCK ON
 SHEETS 2 AND 3 OF PLANS.
  
 17) PROVIDE A DESIGN CERTIFICATION FORM
 OR PROVIDE ALL THE REQUIRED INFORMATION
 ON THE PLANS (MEAN ROOF HEIGHT, DESIGN
 PRESSURE, IMPORTANCE FACTOR, ETC.). SEE
 ATTACHED.
  
 18) STORM PANELS WILL BE REQUIRED ON ALL
 GLAZING THAT IS NOT IMPACT RESISTANT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202