| Plan Review Notes For Permit 01110769 |
| Permit Number |
01110769 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-11 00:00:00 | *************** UNSAT ****************** | | | | | | | | | 1)NOTE: PLEASE CLARIFY IF SERVICE SHOWN | | | IS NEW OR EXISTING? PLEASE NOTE, IF NEW, | | | THERE IS MORE INFORMATION NEEDED. AIC | | | RATING, GROUNDING ELECTRODE DETAIL? | | | PLEASE NOTE THAT NO PANEL SCHEDULES, | | | WERE SUBMITTED.PLEASE SHOW MIN REQ`D | | | CIRCUITS. | | | | | | 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210-8-A-6. | | | | | | 3) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 4) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 5) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BUILDING STEEL AND COLD WATER | | | PER 250-50. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|