Plan Review Notes
Plan Review Notes For Permit 01110769
Permit Number 01110769
Review Stop E
Sequence Number 1
Notes
Date Text
2001-12-11 00:00:00*************** UNSAT ******************
  
  
 1)NOTE: PLEASE CLARIFY IF SERVICE SHOWN
 IS NEW OR EXISTING? PLEASE NOTE, IF NEW,
 THERE IS MORE INFORMATION NEEDED. AIC
 RATING, GROUNDING ELECTRODE DETAIL?
 PLEASE NOTE THAT NO PANEL SCHEDULES,
 WERE SUBMITTED.PLEASE SHOW MIN REQ`D
 CIRCUITS.
  
 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 3) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 4) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 5) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372