| 2001-12-03 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) MORE INFORMATION REQUIRED. INDICATE | | | USAGE FOR SPACE SO THE PROPER MINIMUM | | | FIXTURE REQUIREMENTS CAN BE DETERMINED. | | | 2) DRINKING FOUNTAIN IS REQUIRED PER SPC | | | TABLE 407. | | | 3) SHT A-1, TOILET ACCESS. NOTES #5. TOP | | | OF SEAT TO BE 17" TO 19", NOT 19" TO 20" | | | AS SHOWN. | | | 4) SHT A-1, TOILET DETAIL. FLUSH HANDLE | | | TO BE ON CLEAR SIDE OF TANK PER FACBC | | | SEC 4.16.5. | | | 5) SHT A-2, HDCP TOILET FLOOR PLAN, | | | FLOOR DRAIN NOT VENTED PROPERLY. FLOOR | | | DRAIN SHALL COME OFF LAV DRAIN LINE. | | | 6) SHT A-2, FLOOR DRAIN SHALL BE A MINI- | | | MUM OF 3" AND HAVE A TRAP PRIMER PER SPC | | | SEC 409.4.1.1. | | | 7) SHT A-2, W/C SHALL HAVE A 3" DRAIN, | | | NOT 2" AS SHOWN. ALSO A MINIMUM OF 3" | | | VENT THRU ROOM IS REQUIRED PER SPC SEC | | | 904.3.1 | | | 8) PLEASE PROVIDE A SANITARY AND A WATER | | | RISER DIAGRAM. SHOW ALL PIPE SIZES. SHOW | | | WATER HAMMER ARRESTORS PLACED CLOSE TO | | | FIXTURES IN AN EFFECTIVE RANGE. | | | 9) DEMO INSPECTION REQUIRED FOR ALL FIX- | | | TURES THAT ARE ELIMINATED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|