Date Text
2001-12-03 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) MORE INFORMATION REQUIRED. INDICATE
 USAGE FOR SPACE SO THE PROPER MINIMUM
 FIXTURE REQUIREMENTS CAN BE DETERMINED.
 2) DRINKING FOUNTAIN IS REQUIRED PER SPC
 TABLE 407.
 3) SHT A-1, TOILET ACCESS. NOTES #5. TOP
 OF SEAT TO BE 17" TO 19", NOT 19" TO 20"
 AS SHOWN.
 4) SHT A-1, TOILET DETAIL. FLUSH HANDLE
 TO BE ON CLEAR SIDE OF TANK PER FACBC
 SEC 4.16.5.
 5) SHT A-2, HDCP TOILET FLOOR PLAN,
 FLOOR DRAIN NOT VENTED PROPERLY. FLOOR
 DRAIN SHALL COME OFF LAV DRAIN LINE.
 6) SHT A-2, FLOOR DRAIN SHALL BE A MINI-
 MUM OF 3" AND HAVE A TRAP PRIMER PER SPC
 SEC 409.4.1.1.
 7) SHT A-2, W/C SHALL HAVE A 3" DRAIN,
 NOT 2" AS SHOWN. ALSO A MINIMUM OF 3"
 VENT THRU ROOM IS REQUIRED PER SPC SEC
 904.3.1
 8) PLEASE PROVIDE A SANITARY AND A WATER
 RISER DIAGRAM. SHOW ALL PIPE SIZES. SHOW
 WATER HAMMER ARRESTORS PLACED CLOSE TO
 FIXTURES IN AN EFFECTIVE RANGE.
 9) DEMO INSPECTION REQUIRED FOR ALL FIX-
 TURES THAT ARE ELIMINATED.
  