2001-12-08 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.AIR BALANCE SCHEDULE AS PER 1997
 SMC 501.2.
  
 2.DETAIL OF CONDENSER UNIT STAND.
 AS PER COUNTY WIDE AMENDMENT 1997
 SMC 304.2.5, A MINIMUM OF 18"
 BETWEEN THE ROOF SURFACE AND THE
 BOTTOM OF THE SUPPORT RAIL.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS.
 (1997 SMC 406.1 & NFPA 90A 4-4.4.3)
  