| Plan Review Notes For Permit 01110762 |
| Permit Number |
01110762 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-08 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | 1.AIR BALANCE SCHEDULE AS PER 1997 | | | SMC 501.2. | | | | | | 2.DETAIL OF CONDENSER UNIT STAND. | | | AS PER COUNTY WIDE AMENDMENT 1997 | | | SMC 304.2.5, A MINIMUM OF 18" | | | BETWEEN THE ROOF SURFACE AND THE | | | BOTTOM OF THE SUPPORT RAIL. | | | | | | 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION TO ALARM/STROBE | | | IN NORMALLY OCCUPIED AREAS. | | | (1997 SMC 406.1 & NFPA 90A 4-4.4.3) | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|