2001-11-20 00:00:00******************PROVISO***************
  
 PLEASE NOTE LOCATION OF NEW AHU - ACCESS
 FOR SERVICE SHALL COMPLY WITH 1997 SMC
 304.4.1,ACCESS OPENING SHALL BE NO
 LESS THAN 22" X 36" CONTINUOUS FROM THE
 OPENING TO THE EQUIPMENT AND ITS
 CONTROLS.
  
 A LIGHT ON THE SERVICE SIDE CONTROLLED
 BY A SWITCH AT THE ACCESS OPENING SHALL
 BE PROVIDED.AN ACCESSIBLE DISCONNECT
 SWITCH AND A 110-120 VOLT A/C GROUNDING
 TYPE CONVENIENCE OUTLET CONVENIENT TO
 THE GENERAL EQUIPMENT AREA WILL ALSO BE
 REQUIRED AS PER 1997 SMC 304.4.2
 COUNTYWIDE AMENDMENTS.
  