Plan Review Notes
Plan Review Notes For Permit 01110645
Permit Number 01110645
Review Stop E
Sequence Number 1
Notes
Date Text
2001-11-19 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT A NEW SERVICE
 IS BEING SHOWN, PLEASE SUBMIT AIC
 RATINGS FOR ALL NEW EQUIPMENT BEING
 INSTALLED. 110-9/215-5
  
 2)NOTE: PLEASE NOTE THAT NEW BLDG STEEL/
 FOOTER TO BE PART OF GROUNDING ELECTRODE
 SYSTEM 250-50.
  
 3)NOTE: PLEASE CLARIFY OCP FOR
 TWO NEW PANELS. ONE SHOWS 200A? OTHER?
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 6) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.2
 MECHANICAL CODE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372