| Plan Review Notes For Permit 01110645 |
| Permit Number |
01110645 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-19 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT A NEW SERVICE | | | IS BEING SHOWN, PLEASE SUBMIT AIC | | | RATINGS FOR ALL NEW EQUIPMENT BEING | | | INSTALLED. 110-9/215-5 | | | | | | 2)NOTE: PLEASE NOTE THAT NEW BLDG STEEL/ | | | FOOTER TO BE PART OF GROUNDING ELECTRODE | | | SYSTEM 250-50. | | | | | | 3)NOTE: PLEASE CLARIFY OCP FOR | | | TWO NEW PANELS. ONE SHOWS 200A? OTHER? | | | | | | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 5) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210-8-A-6. | | | | | | 6) PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.2 | | | MECHANICAL CODE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|