2001-12-06 00:00:00PLEASE PROVIDE SIZING DETAILS AND
 CALCULATIONS FOR THE ROOF EMERGENCY
 OVERFLOW SSCUPPERS.SEE SBC 1517.6.4.3.
  
 PROVIDE A BETTER DETAIL FOR THE ATTIC
 VENT DETAIL SHOWN ON SHEET 5 OF 7.
 INCLUDE THE SIZING AND FREE AREA OF THE
 SCREEN.SEE SBC 2309.7.
  
 PROVIDE THE METHOD OF HURRICANE MISSILE
 IMPACT RESISTANT FOR THE EXTERIOR GLAZED
 AREAS. SEE THE ATTACHED IMPLEMENTATION
 STANDARD.
  
 PLEASE PROVIDE THE TEST REPORTS AND/OR
 THE NOTICE OF ACCEPTANCE FOR THE DOORS,
 WINDOWS AND ROOF COVERING.THIS IS
 EXCLUSIVE OF HURRICANE MISSILE IMPACT
 RESISTANT REQUIREMENTS.
  
 THE ADDITION MAY BE SUBJECT TO IMPACT
 FEES COLLECTED BY PALM BEACH COUNTY FOR
 THE CITY.THE PERMIT PLANS MUST BE
 STAMPED BY THAT OFFICE AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.
  
 PLEASE COLLATE THE LOOSE PAGES INTO TWO
 NEAT PLAN SETS.
  
 A NOTICE OF COMMENCEMENT MUST BE
 RECORDED WITH THE CLERK OF THE CIRCUIT
 COURT BEFORE THE PERMIT MAY BE ISSUED.