| Plan Review Notes For Permit 01110620 |
| Permit Number |
01110620 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-20 00:00:00 | 1) NO CUT-SHEETS PROVIDED FOR FIRE | | | SPRINKLER HEADS PLANNED FOR USE. PLEASE | | | PROVIDE CUT-SHEETS. | | | 2) PROVIDE DETAILS FOR FIRE SPRINKLER | | | INSTALLATIONS FOR DUMBWAITER AND TRASH | | | CHUTE(S). | | | 3) PLEASE INDICATE IF THE ONE FIRE | | | DEPARTMENT CONNECTION WILL SERVICE ALL | | | OF THE BUILDINGS LOCATED ON THE CAMPUS. | | | 4) NO FIRE SPRINKLER PROTECTION PROVIDED | | | FOR IT EQUIPMENT ROOM. FM 200 SYSTEM | | | IS NOTED BUT CANNOT BE USED IN LIEU OF | | | REQUIRED FIRE SPRINKLER PROTECTION. | | | 5) HOW WILL PIPE PENETRATIONS BE SEALED | | | THRU RATED FIRE WALLS, ETC. WHO'S | | | RESPONSIBLE FOR IT. | | | 6) PLEASE CLEARLY INDICATE WHY NO | | | FIRE STANDPIPE SYSTEM IS PRESENT IN THE | | | GARAGE. IF THE GARAGE IS THREE STORIES | | | AND MORE THAN FIFTY FEET IN HEIGHT A | | | STANDPIPE SYSTEM WOULD BE REQUIRED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|