| Plan Review Notes For Permit 01110595 |
| Permit Number |
01110595 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-03-15 00:00:00 | THE SCRUBBER UNIT IS REQUIRED TO HAVE | | | ITS OWN INDEPENDENT FIRE SUPPRESSION | | | SYSTEM. PLEASE PROVIDE NOTES ON PLAN | | | AND PROVIDE A SEPARATE PLAN AND PERMIT | | | FOR ITS INSTALLATION. | | | NO DOWNGRADES WILL BE ALLOWED FOR THE | | | EXHAUST DUCT BEYOND THE SCRUBBER UNIT. | | | SOFFIT REVISIONS WERE ALSO PRESENT WITH | | | PLANS. | | | THE FAXED COPY WITH REGARDS TO THE | | | SCRUBBER UNIT THAT WAS SENT TO | | | CONSTRUCTION SERVICES WAS DIFFICULT TO | | | READ. | | | PLANS ARE STAMPED REVISIONS FOR THE | | | HOOD SCRUBBER UNIT. SCRUBBER UNIT IS | | | TO BE BY SEPARATE PLAN AND PERMIT. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|